SEER and SEER2 Rating Comparison Chart

Last updated May 24, 2026

SEER and SEER2 Rating Comparison Chart

Starting January 1, 2023, the U.S. Department of Energy requires new residential cooling equipment to be rated using the SEER2 test procedure (M1 external static pressure, vs. 0.1 in. w.c. for SEER). SEER2 ratings are approximately 4 to 5 percent lower than SEER ratings for the same equipment.

Why SEER2 Numbers Are Lower

The M1 test adds 0.5 in. w.c. of external static pressure to simulate real-world ductwork resistance. Equipment that previously earned a 16 SEER rating in ideal lab conditions typically earns a 15.2 SEER2 under the more realistic test.

Approximate Conversion

Multiply SEER by 0.952 to estimate the SEER2 equivalent:

SEER Approx. SEER2
13 11.7
14 13.3
15 14.3
16 15.2
17 16.2
18 17.1
20 19.0
22 20.9
25 23.8

Minimum Efficiency Standards (2023+)

Region Cooling Min. SEER2
North 13.4
South 14.3
SW 14.3

Source: U.S. DOE Final Rule, 10 CFR Part 430, January 2023; AHRI Standard 210/240-2023.